Symptom |
Possible Remedy |
| No Heat Supply fan will run, combustion
fan does not run.
|
Turn the power off to the furnace for
10 secs, then back on. With the thermostat calling for heat, does
the combustion fan start. If so then your furnace was locked out
on an ignition failure.
With the power off to the furnace, rotate the the shaft, it should
spin freely. If the bearing are tight replace the combustion fan.
|
| Furnace short cycles, temperature uneven
in the house |
On non-electronic thermostats, the cycle rate is
controlled by the anticipator. Remove the front cover, and for access
to the anticipator. This should be set at 0.8 or higher for this
type of furnace.
Check the air supply grills, make sure the air from the furnace
does not blow directly over the thermostat.
If the furnace is over sized, or during mild weather will cause
the furnace to short cycle. |
| No heat- Supply fan will run,
combustion fan runs but the burner will not start. |
Located on or near the vent connection
is a back draft safely control that requires you to manually reset
the device. There maybe another on in the burner compartment near
the burners. This device will trip if hot flue gases spill out from
the chimney or the burner area. Reset the control and determined
the cause. |
| No Heat-Combustion fan will start,
supply fan will run. |
When the thermostat calls for heat, the
combustion fan should start and run for 30 SEC's, then the ceramic
igniter or spark igniter should start. A close visual inspection
of the ceramic igniter may reveal a burn mark or a break in the
ceramic. These igniter seam to last 5-7 years and then they will
burn out or break. Replace the igniter as required. |
This article does not necessarily reflect the
views of 411 Home Repair, and is only a suggestions and/or comments submitted
to our site to share with our site viewers through the world wide web.